SKU
P1500XL

Zurn - P1500XL 3/4" Pressure Relief Valve

  • Field adjustable from 25 to 175 PSI
  • Also suitable for static relief, low capacity pump relief, passive solar, thermal expansion relief and other similar uses in commercial and industrial applications
  • Calibration marks etched on stem
  • Bronze body with stainless steel spring
 
QUANTITY
PRICE /
Quantity (minimum 1):

The Zurn Wilkins P1500XL Calibrated Pressure Relief Valve is installed on cold water service lines to protect against excessive pressure buildup. The P1500XL is for pressure only and should be used in conjunction with other temperature limiting devices.

Application

Ideal where Lead-Free* valves are required. Designed for installation on cold water service lines as a means of protection against excessive pressure buildup. These devices are for pressure only and should be used in conjunction with other temperature limiting devices. Also suitable for static relief, low capacity pump relief, passive solar, thermal expansion relief and other similar uses in commercial and industrial applications.

Standards Compliance
  • Certified to NSF/ANSI 372* by IAPMO R&T
  • *(0.25% MAX. WEIGHTED AVERAGE LEAD CONTENT)
Materials
  • Main valve body - Low Lead Cast Bronze
  • Access covers - Brass
  • Internals - Stainless Steel, Brass
  • Elastomers - Silicone, Buna Nitrile
  • Springs - Stainless steel
Features
  • Maximum working water pressure - 175 PSI
  • Maximum working water temperature - 210°F
  • Hydrostatic test pressure - 175 PSI
  • Threaded connections - (MNPT x FNPT) ANSI B1.20.1
  • (Available 1/2" FNPT outlet only)
Typical Installation

Local codes shall govern installation requirements. Unless otherwise specified, the assembly shall be mounted in accordance with the manufacturers’ instructions and the latest edition of the Uniform Plumbing Code. Assembly shall be installed with adequate drain and sufficient side clearance for testing and maintenance. The installation shall be made so that no part of the unit can be submerged or where relief valve discharge could cause damage.

Specifications

The Pressure Relief Valve shall be certified to NSF/ANSI 372, consisting of a low lead bronze body and an internally-loaded "poppet" type pressure sensing member. The main body shall have a male pipe thread on the inlet and a female pipe thread on the outlet. The Pressure Relief Valve shall be a ZURN WILKINS Model P1500XL, P1520XL or P1550XL.

Brand
Zurn Industries LLC
Color
Brass
Material
Cast Brass
Max Operating Temperature
210° F
Max Total Pressure
175 PSI
  • Zurn - Safety Relief Valve Opening and Closing Points
New Retail Customers

Creating a Retail Account has many benefits: faster checkout, save multiple addresses, track orders, create wish lists, and more.

Existing Reinders Business Customers

You can quickly connect your existing business account for a simplified shopping experience. Receive all the benefits of a Retail Account plus custom pricing, real-time inventory, access to special promotions, pay your bills online, quick order, and more.

Don’t have a Reinders Business Account yet?

Apply Today!